Metering Units represent the secondary values for the current and voltage transformers. That is Metering Units are the values present at the voltage and current inputs at the back of the meter.
As an example, if the PTs (voltage transformers) have a ratio of 480:120 and the CTs (current transformer) have a ratio of 300:5; and you were injecting full secondary values (120 Vl-l and 5 A) for all three phases you would see the the following values:
kw A = 120 V * 5 A = 600 W = 0.600 kW
kw B = 120 V * 5 A = 600 W = 0.600 kW
kw C = 120 V * 5 A = 600 W = 0.600 kW
kw total = 0.600 kw + 0.600 kw + 0.600 kw = 1.80 kw
Comments
Post a Comment
With well over 30,000+ firms offering Switchgear, Control Panel Transformer Repairing & Modification service. We know how challenging it can be to find the right agency for your requirement needs.
At Panja Power we hold one goal above all others: 100% client satisfaction. Our in-house team of panel board repairing, modification, manufacturing , design uphold the highest standards for project planning and execution, and we’re dedicated to building the perfect work for your company on-time and on-budget